YY-Z-ST Dca | JOB_0157712 | JOB_0157712
Indoor telecommunication & Fire alarm cables

YY-Z-ST Dca

02.09.05_JOB

|

Use of Cable

installation cable with steelwired braided and alluminium foil for vulnerable areas. For telecommunication and IT-systems for lossless data and signal transmission. Suitable for fixed laying in dry and humid rooms, on-wall and in-wall, outdoor use, and laying underground.

Product variants
Product information "YY-Z-ST Dca"
Special features
  • shielded by plastic-clad aluminium foil
  • pairs stranded in bundles (Bd)
  • free from lacquer damaging substances and silicone (during production)
Remarks
  • conform to RoHS
  • conform to 2006/95/EC-Guideline CE
  • installation cables are not designed for high voltage purposes
Conductor material: Copper conductor blank
Conductor class: Conductor-Ø 0,8 mm (0,50 mm²)
Core insulation: PVC
Core identification: Acc. to NEN 1597 different colours
Stranding: Cores stranded to twisted pairs
Shield3: Plastic-clad aluminium foil
Outer sheath: PVC
Sheath colour: Green RAL 6018 (GN)
Rated voltage: 300 V
Testing voltage: 1500 V
Conductor resistance: Loop: 0,8 max 36,6 Ω / km
Insulation resistance: Min. 100 MΩ x km
Capacity: Max. 100 nF/km
Min. bending radius fixed: 7,5 x d
Min. bending radius moved: 10 x d
Operat. temp. fixed min/max: -20 °C / +70 °C
Operat. temp. moved min/max: +5 °C / +70 °C
Burning behavior: Flame-retardant acc. to DIN EN 60332.3 , IEC 60332-1 EN 50399
Standard: EN 13501-6 / EN 50575 Dca s2d2a3 / K102-314 /EN 60.332.3.24 (F2) / UV: ISO 4892-2

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
YY-Z-ST Dca 02.09.05_JOB
Indoor telecommunication & Fire alarm cables
300V, shielded, overall metal foil & steel wire braid, CPR Dca s2d2a3
Item count 9