SIMX-P | JOB_0117900 | JOB_0117900
Icon static Icon flexible
Silicone insulated cables from -60 up to +180°C

SIMX-P

08.04.05_JOB

|

Use of Cable

heat and coldness resistant power, control and connecting cable in electrical facilities, for lossless data and signal transmission, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms and outdoor use, no laying underground.

Product variants
Icon einsatzort indoor Icon einsatzort outdoor
Icon merkmale uv resistent Icon merkmale kein feuer Icon merkmale halogenfrei
Icon standards ce geschuetzt
Product information "SIMX-P"
Special features
  • largely resistant to acids, bases and specified types of oil
  • no flame conduction in case of fire, insulation integrity and low smoke density
  • silicone is resistant to ozone, oxygen and sea water and weather-proofed
  • triple protection for high mechanical requirements and magnetic shield (glass silk taping with additional oxidation-proofed steel wire braid)
  • above +100 °C and with exclusion of air, the mechanical properties of silicone cables
    will be reduced early, adequate ventilation should be ensured
Remarks
  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: Copper strand tinned
Conductor class: Acc. to IEC 60228 cl. 5
Core insulation: Silicone
Core identification: Up to 5 cores acc. to DIN VDE 0293-308 coloured cores; from 6 cores black cores with white numerals with or without GNYE
Stranding: Stranded in layers
Inner sheath material: Silicone
Shield3: Glass-silk-braid - steel wire braid zinced; coverage approx. 85%, over glass-silk braid
Outer sheath: Glass-silk-braid - steel wire braid zinced; coverage approx. 85%, over glass-silk braid
Sheath colour: Metal
Rated voltage: Uo/U 300/500 V;
Testing voltage: 2 kV
Conductor resistance: At +20 °C acc. to IEC 60228 cl. 5
Insulation resistance: Min. 2,0 GΩ x km
Current-carrying-capacity: Acc. to DIN VDE, see Technical Guidelines
Min. bending radius fixed: 5 x d
Min. bending radius moved: 10 x d
Operat. temp. fixed min/max: -60 °C / +180 °C; short-time: +200 °C (when using adequate conductor materials)
Temp. at conductor: +180 °C
Halogen free: Halogen-free acc. to IEC 60754-1
Corrodibility: Acc. to IEC 60754-2
Burning behavior: Self-extinguishing and flame-retardant acc. to IEC 60332-1-2
SIMX JB/OB & JZ/OZ 08.04.03_JOB
Silicone insulated cables from -60 up to +180°C
300/500V, unshielded, halogen-free, fine stranded
Item count 71