BUS | FIELDBUS cables for industrial & process automation
MULTIBUS & INTERBUS 100 - 120 Ohm - HF
03.10.02.02
|
Use of Cable
MULTIBUS - as fieldbus cable for use in a variety of fieldbus systems such as DIN measuring bus, BITBUS (IEEE 1118), Local Operating Network (LON) SUCOnet P, Modulink-P, P-VariNet, FIP ...
and
INTERBUS - as remote bus cable (Type RBC) or installation remote bus with integrated power supply (type INBC) in the field of production automation, for high flexible applications (e.g. power chains, gantry robots, pick and place units, conveyors, machine tools, automated production systems, etc.)
Product information "MULTIBUS & INTERBUS 100 - 120 Ohm - HF"
Special features
- low adhesion
- largely resistant to lubricants, coolants fluids and grease
- oil-resistant: acc. to DIN EN 60811-2-1
- UV-resistant
- EMC compliant shielding
- max. cable lengths for a bus segment acc.to PI at stated transmission rate:
MULTIBUS: 93,75kbit/s-max.1,2km | 187,5kbit/s-max.1km | 0,5Mbit/s-max.400m
1,5 Mbit/s-max.200m | 12,0 Mbit/s-max.100m
INTERBUS: 0,5Mbit/s-max.400m
- conform to RoHS
- conform to DESINA (violet)
- conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
- LABS-/silicone-free (during production)
- FRNC: Flame Retardant Non Corrosive, halogen free
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Super fine wired acc. to IEC 60228 cl. 6 |
Core insulation: | BUScores: Polyolefine, supply cores: PVC |
Core identification: | BUScores: acc. to DIN 47100, supply cores: rd, bu, gnye |
Stranding: | BUScores stranded to a pair |
Overall stranding: | (INBC) BUSelem. a. supply cores stranded |
Shield3: | Copper braid tinned |
Outer sheath: | PUR |
Sheath colour: | Violet RAL 4001 (VT) |
Rated voltage: | BUScores: 250 V (not for high voltage purposee); supply cores: 500 V |
Testing voltage: | 1,5 kV |
Loop resistance: | Max. 159,8 Ω/km - 0,25 mm²: max. 39,0 Ω/km 1,0 mm² |
Capacity: | Max. 60 nF/km |
Characteristic impedance: | MULTIBUS: 100 - 120 Ω; INTERBUS: 100 Ω +/- 15 Ω |
Min. bending radius fixed: | 5 x d |
Min. bending radius moved: | 7,5 x d < 3mTL* | 15 x d ≥ 3mTL*, |
Operat. temp. fixed min/max: | - 40 °C / +80 °C |
Operat. temp. moved min/max: | - 30 °C / +70 °C |
Halogen free: | Acc. to IEC 60754-1 (FRNC Typen) |
Burning behavior: | Flame retardant acc. to IEC 60332-1-2; CMX: acc. to IEC 60332-1-2, VW-1 |
Resistant to oil: | Acc. to DIN EN 60811-2-1 |
Approvals: | UL/CSA - cULus 300V, 75°C, CMX/SunRes/OilRes |
Speed: | Self-supporting: 4 m/s |
Acceleration: | Max. 5 m/s² |
Bending cycles: | Up to 7,5 Mio. |
There aren't any asked questions yet.
ASi-BUS Aktor Sensor Interface
03.10.06.01
BUS | FIELDBUS cables for industrial & process automation
for fixed installation & limited flexible applications, UL/CSA
for fixed installation & limited flexible applications, UL/CSA
Item count
10
PROFIBUS DP / FMS / FIP 150 Ohm
03.10.01.01
BUS | FIELDBUS cables for industrial & process automation
fixed installation & limited flexible applications, UL/CSA, different CPR versions available
fixed installation & limited flexible applications, UL/CSA, different CPR versions available
Item count
11
DeviceNet 120 Ohm
03.10.04.01
BUS | FIELDBUS cables for industrial & process automation
for fixed installation & limited flexible applications, UL/CSA
for fixed installation & limited flexible applications, UL/CSA
Item count
4
DeviceNet 120 Ohm - HF
03.10.04.02
BUS | FIELDBUS cables for industrial & process automation
for high flexible applications (drag chain) UL/CSA
for high flexible applications (drag chain) UL/CSA
Item count
4