KEMAFLEX KVCY-JZ /OZ Dca S3 | JOB_T1003498 | JOB_T1003498
Icon static Icon flexible
Approved PVC control cables

KEMAFLEX KVCY-JZ /OZ Dca S3

01.02.02_JOB

|

Use of Cable

power, control and connecting cable in electrical facilities, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.

Product variants
Icon einsatzort indoor
Icon abschirmung Icon merkmale kein feuer Icon merkmale oelresistent
Icon standards ce geschuetzt Icon standards cpr d ca Icon standards ema eur geschuetzt
Product information "KEMAFLEX KVCY-JZ /OZ Dca S3"
Special features
  • KEMA
  • 4 kV testing voltage
  • no storage outdoors or in wet rooms 
  • JZ/OZ: 300/500 V
  • largely resistant to acids, bases and specified types of oil 
  • triple protection for high mechanical requirements.
Remarks
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request
Conductor material: Bare copper strand
Conductor class: Acc. to CEI 20-29 cl. 5 and DIN-VDE 0295 K5
Core insulation: PVC
Core identification: JZ/OZ: acc. to DIN VDE 0293 black cores with white numerals with or without GNYE
Stranding: Stranded in layers
Inner sheath material: PVC
Inner sheath colour: Grey, RAL 7001
Shield3: Copper braid tinned; coverage approx. 80 %
Sheath colour: Grey, RAL 7001
Rated voltage: Uo/U - JZ/OZ: 300/500 V
Testing voltage: 3 kV
Conductor resistance: 0,50mm² - max. 39,0 Ohm / km; 0,75mm² - max. 26,0 Ohm / km1,00mm² - max. 19,5 Ohm / km; 1,50mm² - max. 13,3 Ohm / km2,50mm² - max. 7,98 Ohm / km
Insulation resistance: Min. 20 MΩ x km
Current-carrying-capacity: Acc. to DIN VDE, see technical Guidelines
Min. bending radius fixed: 8 x d
Min. bending radius moved: 12 x d
Operat. temp. fixed min/max: -30 °C / +80 °C
Operat. temp. moved min/max: -5 °C / +80 °C
Temp. at conductor: +70 °C in operation; +150 °C in case of short-circuit
Burning behavior: Self-extinguishing & flame-retardant acc.to DIN EN 60332-1-3 / DIN EN 60332-3-24 C
Resistant to oil: PVC TM5 nach DIN EN 50363-4-1ölbeständig nach DIN EN 60811-404
TRIOFLEX CY-JZ/OZ Eca 01.02.04_JOB
Approved PVC control cables
300/500V (IEC), 600V (UL), shielded, HAR, UL/CSA, CPR Eca
Item count 130
TRIOFLEX CC-JZ/OZ Eca 01.02.03_JOB
Approved PVC control cables
300/500V (IEC), 600V (UL), unshielded, HAR, UL/CSA, CPR Eca
Item count 139