Approved PVC control cables
KEMAFLEX KVCY-JZ /OZ Dca S3
01.02.02_JOB
|
Use of Cable
power, control and connecting cable in electrical facilities, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.
Product information "KEMAFLEX KVCY-JZ /OZ Dca S3"
Special features
- KEMA
- 4 kV testing voltage
- no storage outdoors or in wet rooms
- JZ/OZ: 300/500 V
- largely resistant to acids, bases and specified types of oil
- triple protection for high mechanical requirements.
- conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
- LABS-/silicone-free (during production)
- We are pleased to produce special versions, other dimensions, core and jacket colours on request
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Acc. to CEI 20-29 cl. 5 and DIN-VDE 0295 K5 |
Core insulation: | PVC |
Core identification: | JZ/OZ: acc. to DIN VDE 0293 black cores with white numerals with or without GNYE |
Stranding: | Stranded in layers |
Inner sheath material: | PVC |
Inner sheath colour: | Grey, RAL 7001 |
Shield3: | Copper braid tinned; coverage approx. 80 % |
Sheath colour: | Grey, RAL 7001 |
Rated voltage: | Uo/U - JZ/OZ: 300/500 V |
Testing voltage: | 3 kV |
Conductor resistance: | 0,50mm² - max. 39,0 Ohm / km; 0,75mm² - max. 26,0 Ohm / km1,00mm² - max. 19,5 Ohm / km; 1,50mm² - max. 13,3 Ohm / km2,50mm² - max. 7,98 Ohm / km |
Insulation resistance: | Min. 20 MΩ x km |
Current-carrying-capacity: | Acc. to DIN VDE, see technical Guidelines |
Min. bending radius fixed: | 8 x d |
Min. bending radius moved: | 12 x d |
Operat. temp. fixed min/max: | -30 °C / +80 °C |
Operat. temp. moved min/max: | -5 °C / +80 °C |
Temp. at conductor: | +70 °C in operation; +150 °C in case of short-circuit |
Burning behavior: | Self-extinguishing & flame-retardant acc.to DIN EN 60332-1-3 / DIN EN 60332-3-24 C |
Resistant to oil: | PVC TM5 nach DIN EN 50363-4-1ölbeständig nach DIN EN 60811-404 |
There aren't any asked questions yet.
TRIOFLEX CY-JZ/OZ Eca
01.02.04_JOB
Approved PVC control cables
300/500V (IEC), 600V (UL), shielded, HAR, UL/CSA, CPR Eca
300/500V (IEC), 600V (UL), shielded, HAR, UL/CSA, CPR Eca
Item count
130
TRIOFLEX CC-JZ/OZ Eca
01.02.03_JOB
Approved PVC control cables
300/500V (IEC), 600V (UL), unshielded, HAR, UL/CSA, CPR Eca
300/500V (IEC), 600V (UL), unshielded, HAR, UL/CSA, CPR Eca
Item count
139