EQ SO-JB/OB & JZ/OZ Eca

01.01.07_JOB

|

Use of Cable

power, control and connecting cable in electrical facilities, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.

Product variants
Icon einsatzort indoor
Icon merkmale kein feuer Icon merkmale oelresistent
Icon standards ce geschuetzt Icon standards cpr e ca
Product information "EQ SO-JB/OB & JZ/OZ Eca"
Special features
  • 4 kV testing voltage
  • no storage outdoors or in wet rooms 
  • JZ/OZ: 300/500 V, JB/OB: 0,6/1 kV (from 25 mm²) 
  • largely resistant to acids, bases and specified types of oil 
  • triple protection for high mechanical requirements and magnetic shield (oxidation-proofed steel wire braid and additional inner sheath)
Remarks
  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request
Conductor material: Bare copper strand
Conductor class: Acc. to IEC 60228 cl. 5
Core insulation: PVC
Core identification: JZ/OZ: acc. to DIN VDE 0293 black cores with white numerals; JB/OB: coloured - up to 5 cores acc. to DIN 293-308, from 6 cores CCG colour code (see technical guideline) G: with GNYE
Stranding: Stranded in layers
Inner sheath material: PVC
Shield3: Steel wire braid zinced
Outer sheath: PVC
Sheath colour: Transparent
Rated voltage: Uo/U - JZ/OZ: 300/500 V || JB/OB: 0,6/1 kV
Testing voltage: 4 kV
Conductor resistance: Acc. to IEC 60228 cl. 5
Insulation resistance: Min. 20 MΩ x km
Current-carrying-capacity: Acc. to DIN VDE, see technical Guidelines
Min. bending radius fixed: 6 x d
Min. bending radius moved: 15 x d
Operat. temp. fixed min/max: -30 °C / +80 °C
Operat. temp. moved min/max: -15 °C / +70 °C
Temp. at conductor: +70 °C in operation; +150 °C in case of short-circuit
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1
Standard: Similar to EN 50525-2-51| 0,6/1 kV-type: with insulation thickness for 1 kV
EQ CC -JZ/OZ Eca 01.01.04_JOB
PVC Control cables
300/500V, unshielded, CPR Eca
Item count 201
EQ CY-JZ/OZ Eca 01.01.06_JOB
PVC Control cables
300/500V, 0,6/1kV, shielded, transparent, CPR Eca
Item count 116
EQ SO-JB/OB & JZ/OZ Eca 01.01.07_JOB
PVC Control cables
300/500V, steel wire braided, CPR Eca
Item count 132
EQ CC -JB/OB Eca 01.01.01_JOB
PVC Control cables
300/500V, 450/750V, 0,6/1kV, unshielded, CPR Eca
Item count 119