PVC Control cables
EQ SO-JB/OB & JZ/OZ Eca
01.01.07_JOB
|
Use of Cable
power, control and connecting cable in electrical facilities, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.
Product information "EQ SO-JB/OB & JZ/OZ Eca"
Special features
- 4 kV testing voltage
- no storage outdoors or in wet rooms
- JZ/OZ: 300/500 V, JB/OB: 0,6/1 kV (from 25 mm²)
- largely resistant to acids, bases and specified types of oil
- triple protection for high mechanical requirements and magnetic shield (oxidation-proofed steel wire braid and additional inner sheath)
- conform to RoHS
- conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
- LABS-/silicone-free (during production)
- We are pleased to produce special versions, other dimensions, core and jacket colours on request
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Acc. to IEC 60228 cl. 5 |
Core insulation: | PVC |
Core identification: | JZ/OZ: acc. to DIN VDE 0293 black cores with white numerals; JB/OB: coloured - up to 5 cores acc. to DIN 293-308, from 6 cores CCG colour code (see technical guideline) G: with GNYE |
Stranding: | Stranded in layers |
Inner sheath material: | PVC |
Shield3: | Steel wire braid zinced |
Outer sheath: | PVC |
Sheath colour: | Transparent |
Rated voltage: | Uo/U - JZ/OZ: 300/500 V || JB/OB: 0,6/1 kV |
Testing voltage: | 4 kV |
Conductor resistance: | Acc. to IEC 60228 cl. 5 |
Insulation resistance: | Min. 20 MΩ x km |
Current-carrying-capacity: | Acc. to DIN VDE, see technical Guidelines |
Min. bending radius fixed: | 6 x d |
Min. bending radius moved: | 15 x d |
Operat. temp. fixed min/max: | -30 °C / +80 °C |
Operat. temp. moved min/max: | -15 °C / +70 °C |
Temp. at conductor: | +70 °C in operation; +150 °C in case of short-circuit |
Burning behavior: | Self-extinguishing & flame-retardant acc.to IEC 60332-1 |
Standard: | Similar to EN 50525-2-51| 0,6/1 kV-type: with insulation thickness for 1 kV |
There aren't any asked questions yet.
EQ CY-JZ/OZ Eca
01.01.06_JOB
PVC Control cables
300/500V, 0,6/1kV, shielded, transparent, CPR Eca
300/500V, 0,6/1kV, shielded, transparent, CPR Eca
Item count
116
EQ SO-JB/OB & JZ/OZ Eca
01.01.07_JOB
PVC Control cables
300/500V, steel wire braided, CPR Eca
300/500V, steel wire braided, CPR Eca
Item count
132
EQ CC -JB/OB Eca
01.01.01_JOB
PVC Control cables
300/500V, 450/750V, 0,6/1kV, unshielded, CPR Eca
300/500V, 450/750V, 0,6/1kV, unshielded, CPR Eca
Item count
119