EQ CY-JZ/OZ Eca | JOB_T0502582 | JOB_T0502582
Icon static Icon flexible
PVC Control cables

EQ CY-JZ/OZ Eca

01.01.06_JOB

|

Use of Cable

power, control and connecting cable in electrical facilities for lossless data and signal transmission, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.

Product variants
Icon einsatzort indoor
Icon abschirmung Icon merkmale kein feuer Icon merkmale oelresistent
Icon standards ce geschuetzt Icon standards cpr e ca
Product information "EQ CY-JZ/OZ Eca"
Special features
  • 3 kV testing voltage
  • largely resistant to acids, bases and specified types of oil
  • space-saving alternative to LIYYCY-JZY
  • EMC compliant shielding
Remarks
  • conform to RoHS
  •  conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • special versions, other dimensions, core and jacket colours according to your specifications on request
Conductor material: Bare copper strand
Conductor class: Acc. to IEC 60228 cl. 5
Core insulation: PVC
Core identification: Black cores with white numbers; With or without GNYE
Stranding: Stranded in layers
Shield3: Copper braid tinned, coverage approx. 85 %
Outer sheath: PVC
Sheath colour: Grey, RAL 7001
Rated voltage: Uo/U: 300/500 V
Testing voltage: 3 kV
Conductor resistance: Acc. to IEC 60228 cl. 5
Insulation resistance: Min. 20 MΩ x km
Current-carrying-capacity: Acc. to DIN VDE, see technical Guidelines
Capacity: Core/core ca. 120 nF/km; core/shield ca. 160 nF/km
Inductivity: Ca 0,65 mH/km
Min. bending radius fixed: 6 x d
Min. bending radius moved: 20 x d
Operat. temp. fixed min/max: -40 °C / +80 °C
Operat. temp. moved min/max: -5 °C / +70 °C
Temp. at conductor: +70 °C in operation; +150 °C in case of short-circuit
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1
Resistant to oil: Acc. to EN 50290-2-22 / VDE 0819-102 (TM54)
Standard: Oil resistant according: DIN EN 50290-2-22 resp. VDE 0819-102, TM54. The cable is conform to Low Voltage Directive (LVD) 2014/35/EC CE
EQ CC -JZ/OZ Eca 01.01.04_JOB
PVC Control cables
300/500V, unshielded, CPR Eca
Item count 201
EQ CY-JZ/OZ Eca 01.01.06_JOB
PVC Control cables
300/500V, 0,6/1kV, shielded, transparent, CPR Eca
Item count 116
EQ SO-JB/OB & JZ/OZ Eca 01.01.07_JOB
PVC Control cables
300/500V, steel wire braided, CPR Eca
Item count 132
EQ CC -JB/OB Eca 01.01.01_JOB
PVC Control cables
300/500V, 450/750V, 0,6/1kV, unshielded, CPR Eca
Item count 119