EQ CKY Eca | JOB_1011205 | JOB_1011205
Icon static Icon flexible
Electronic cables

EQ CKY Eca

02.01.04_JOB

|

Use of Cable

data transmission cable, control and connecting cable predominantly for transmission of analog and digital signals in process controlled facilities in measurement and control technology for lossless transmission of data and signals. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.

Product variants
Icon einsatzort indoor
Icon abschirmung Icon merkmale kein feuer Icon merkmale oelresistent
Icon standards ce geschuetzt Icon standards cpr e ca
Product information "EQ CKY Eca"
Special features
  • twisted pairs
  • largely resistant to acids, bases and specified types of oil
  • free from lacquer damaging substances and silicone (during production)
  • recommended for EMC-applications
Remarks
  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • also available as unscreened version
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: Bare copper strand
Conductor class: Acc. to IEC 60228 cl. 5; exception: 0,34 mm², stranded (7 x 0,25 mm)
Core insulation: PVC
Core identification: Acc. to DIN 47100 different colours
Stranding: 2 cores twisted to a pair; pairs stranded in layers
Shield3: Copper braid tinned; coverage approx. 85%
Outer sheath: PVC
Sheath colour: Grey, RAL 7032
Rated voltage: 250 V; peak-voltage on 0,14 mm²: 350 V; > 0,14 mm²: 500 V
Testing voltage: On 0,14 mm² core/core: 1,2 kV; core/shield: 1,0 kV > 0,14 mm²: core/core: 1,5 kV; core/shield: 1,0 kV
Conductor resistance: Acc. to IEC 60228 cl. 5
Insulation resistance: Min. 20 MΩ x km
Current-carrying-capacity: Acc. to DIN VDE, see Technical Guidelines
Capacity: Core/core ca. 120 nF/km; core/shield ca. 160 nF/km
Min. bending radius fixed: Up to 12 mm Ø: 5 x d; up to 20 mm Ø: 7,5 x d; > 20 mm Ø: 10 x d
Min. bending radius moved: Up to 12 mm Ø: 10 x d; up to 20 mm Ø: 15 x d; > 20 mm Ø: 20 x d
Operat. temp. fixed min/max: -30 °C / +80 °C
Operat. temp. moved min/max: -5 °C / +70 °C
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1
Standard: Similar to DIN VDE 0812
EQ CY Eca 02.01.02_JOB
Electronic cables
DIN47100, 250V, shielded, CPR Eca
Item count 174
EQ CKY Eca 02.01.04_JOB
Electronic cables
DIN47100, 250V, twisted pairs, shielded, CPR Eca
Item count 91