CAN BUS - ControlerAreaNetwork 120 Ohm | JOB_9568061 | JOB_9568061
Icon static
BUS | FIELDBUS cables for industrial & process automation

CAN BUS - ControlerAreaNetwork 120 Ohm

03.10.03.01

|

Use of Cable

as fieldbus cables for CAN (Controller Area Network) systems, in the field of factory automation, for fixed installation & flexible applications.

This bussystem has its origins in the automotive sector and has established itself in the field of production automation.

Standard acc. to CAN Spec.: ISO 11898

Product variants
Icon einsatzort indoor Icon einsatzort outdoor Icon einsatzort unterirdisch
Icon abschirmung Icon merkmale uv resistent Icon merkmale kein feuer Icon merkmale oelresistent
Icon standards ce geschuetzt Icon standards ul csa
Product information "CAN BUS - ControlerAreaNetwork 120 Ohm"
Special features
  • largely resistant to grease, coolant fluids and lubricants
  • oil-resistant: acc. to DIN EN 60811-2-1 (only mineral oil))
  • UV-resistant (TRAY & BURIAL)
  • direct burial (BURIAL)
  • EMC compliant shielding
  • max. transmission rate: 1 Mbit/s at 40m segment length
  • max. cable lengths for a bus segment depending on the cross section
                0- 40 m AWG24, AWG22 | 40-300 m AWG22, AWG20 |
                300-600 m AWG20 | 600-1.000 m AWG19
Remarks
  • conform to RoHS
  • conform to DESINA (violet)
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
Conductor material: Copper conductor blank
Conductor class: 0,22, 0,34 & 0,5mm²: 7-wired; fine wired acc. to IEC 60228 cl. 5
Core insulation: Foamed PE/PP
Core identification: Acc. to DIN VDE 47100
Stranding: Cores twisted to pairs, TRAY-version: star quad
Inner sheath material: TRAY: PVC
Shield3: Copper braid tinned
Outer sheath: PVC resp. BURIAL: PVC/PE
Sheath colour: Violet RAL 4001 (VT) or black (BK)
Rated voltage: 250 V (not for high voltage purposes)
Testing voltage: 1,5 kV
Loop resistance: Max. 175,2 Ω/km - AWG 24, max. 110,8 Ω/km - AWG 22; max. 68,8 Ω/km - AWG 20; max 55,0 Ω/km - AWG 19
Capacity: Nom. 40 nF/km
Characteristic impedance: 120 Ω +/- 12 Ω
Min. bending radius fixed: 7,5 x d
Min. bending radius moved: 15 x d
Operat. temp. fixed min/max: -40 °C / +80 °C
Operat. temp. moved min/max: -10 °C / +70 °C
Burning behavior: PE: not flame retardant | PVC CMX: flame retardant acc. to IEC 60332-1-2, VW-1 | TRAY: acc. to IEC 60332-3-24 (Cat.C), FT4
Resistant to oil: Acc. to DIN EN 60811-2-1 (only mineral oil)
Approvals: UL/CSA - cULus 300V, 75°C, CMX | TRAY: cULus 300V, 75°C, CMG/PLTC-ER/SunRes/OilRes
ASi-BUS Aktor Sensor Interface 03.10.06.01
BUS | FIELDBUS cables for industrial & process automation
for fixed installation & limited flexible applications, UL/CSA
Item count 10
PROFIBUS DP / FMS / FIP 150 Ohm 03.10.01.01
BUS | FIELDBUS cables for industrial & process automation
fixed installation & limited flexible applications, UL/CSA, different CPR versions available
Item count 11
MULTIBUS & INTERBUS 100 - 120 Ohm - HF 03.10.02.02
BUS | FIELDBUS cables for industrial & process automation
for high flexible applications (drag chain) UL/CSA
Item count 7
DeviceNet 120 Ohm 03.10.04.01
BUS | FIELDBUS cables for industrial & process automation
for fixed installation & limited flexible applications, UL/CSA
Item count 4